Chapter 6 PLC Link

6

When a photoelectric sensor for trigger input is connected to the BL series, do not
use this area.
Specify this area as follows:

• Start reading (Trigger ON): 0001
• End reading (Trigger OFF): 0000

Note: Specify this area as “0000” while the BL series is not reading bar code data.

The ID number of the BL series that read the data is stored in the +02 address.
The number of data digits is stored in the +03 address as binary data.

The read bar code data is stored in the +04 to +258 addresses using the ASCII
codes (Hexadecimal numbers in two digits) by the digit. (See the ASCII code
table on p.134.)

If a read error occurs, the “ERROR” code is stored in the corresponding area.
(The read error code can be easily changed according to the BL series’ setting.)

If the buffer overflow error occurs with the BL series, the “OVER” code is stored
in the corresponding area.

Note: These data areas accept up to 255 digits. However, the BL series can read
only 32 digits. Therefore, all of the areas for 255 digits are not used for the N-400.
Only the areas corresponding to the number of the data digits are used.

Example: When the BL series reads bar code data as “KE12”:

Example: When a read error (ERROR) occurs:

+02 to +258

Data (ID number, number of digits, data) memory area

A+02

ID number (1 to 31)

A+03

Number of digits of bar code data (1 to 255)

A+04

1st digit of read data

A+05

2nd digit of read data

:

:

A+258

255th digit of read data

+ 02

12

+ 03

4

+ 04

$004B

+ 05

$0045

+ 06

$0031

+ 07

$0032

ID number

Number of digits

Specified by ASCII codes
(hexadecimal numbers)

"K"

"E"

"1"

"2"

+ 02

1

+ 03

5

+ 04

$0045

+ 05

$0052

+ 06

$0052

+ 07

$004F

+ 08

$0052

ID number

Number of digits

Specified by ASCII codes
(hexadecimal numbers)

"E"

"R"

"R"

"O"

"R"