Sizing of copper discharge pipe "D2" for common

temperature relief

Valve outlet size

Minimum size of discharge

pipe D1

Minimum size of discharge

pipe D2 from tundish

Maximum resistance

allowed, expressed as a

length of straight pipe (i.e.

no elbows or bends

Resistance created by each

elbow or bend

G1/2

15mm

22mm

Up to 9m

0.8m

28mm

Up to 18m

1.0m

35mm

Up to 27m

1.4m

G3/4

22mm

22mm

Up to 9m

1.0m

28mm

Up to 18m

1.4m

35mm

Up to 27m

1.7m

G1

28mm

22mm

Up to 9m

1.4m

28mm

Up to 18m

1.7m

35mm

Up to 27m

2.3m

The above table is based on copper tube. Plastic pipes may be

of different bore and resistance. Sizes and maximum lengths of

plastic should be calculated using data prepared for the type of

pipe being used.

Worked example

The product is supplied with a G1/2 T&P valve the pipe D2 is

measured to be 4m in length from the tundish to the point of

discharge with 4 elbows.

7m of 22mm pipe = 4m

4 22mm elbows = 0.8 X 4 = 3.2m

3.2 + 4 = 7.2m and permissable in 22mm pipe should the

calculation not be permissable in 22mm the pipe must be

increased to 28 or even 35mm copper pipe or internal diameter

equivilent.

If in multiple dwellings a common discharge pipe is used it

should be at least one pipe size larger than the largest individual

discharge pipe to be connected.

Connection into soil stacks

Under normal circumstances it is not permissable to discharge

the pipe (D2) into a soil stack unless the following conditions are

met

1. The soil stack and its seals are clearly designed and marked

to withstand the temperatures of the water which could be

discharged under fault conditions.

2. A mecahnical type seal trap is used (water traps are not

permitted) with a temperature rating defined as above

3. It is a separate branch pipe with no other sanitary appliances

connected to it.

4. If the branch pipe used is plastic it must be either

- a. Polybutalene (PB) Class S of BS 7921-2:2006

- b. Cross linked polyethylene (Pe-X) Class S of BS 7921-3:2006

- c. A continuous marking applied to the pipe to warn that no

sanitary appliance may be fitted to it

Termination of the discharge pipe

i

The discharge pipe must terminate in a safe place where

there is no risk to persons in the vicinity of the discharge.

Acceptable terminations are

1. Into a trapped gully, the end of the pipe may be below the

grating but above the water seal

2. Facing downward and up to 100mm above an external surface

(providing a type of wire cage is fitted to prevent contact)

3. Discharged at a high level into a metal hopper and downpipe

(the end of the pipe must be visible)

4. Discharged onto a roof providing that

- a. The roof is constructed of a material designed to withstand

the temperatures

- b. The gutter or drain system connected to the roof is at least

3m away from the point of discharge

b

The tundish should be installed so that is is visible to

the occupants and is positioned away from electrical

devices.

b

The discharge pipes (tundishes) drain valves

etc. shall be positioned away from any electrical

components.

b

Cylinder relief valve connections should not be used

for any other purposes.

b

No valve should be fitted between the expansion

valve and the storage cylinder.