0020112185_PROTO_13 - 01/11 - Glow-worm

- 51 -

19.3.2

DHW expansion vessel

Drain the boiler domestic hot water circuit as described in the

appropriate chapter "Draining".

1

3

2

4

5

Key

1 Expansion vessel

2 Expansion vessel pipe

3 nut

4 bracket

Drain the boiler domestic hot water circuit as described in the

appropriate chapter "Draining".

• Undo the expansion vessel pipe (2).

• Remove nut (3).

• Remove the expansion vessel (1).

19.3.3

Particle filter

1

2

Key

1

Particle filter

2 Clips

i

Remove the particle filter to check its condition.

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Remove the 2 clips (2).

• Remove the particle filter (1).

• After installing a new particle filter, refill and bleed the

appliance and the installation if necessary.

MAINTENANCE