9.2.2

Vertical concentric flue Ø 60/100 mm

or Ø 80/125 mm (C33 type installation)

L

Type

Max length (L)

Ø 60/100

10 m

Ø 80/125

13 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.

9.2.3

Multiple boiler chimney flue

Ø 60/100 mm (C43 type installation)

b

The flue connecting from the appliance to the flue

system must be supplied from the manufacturer of the

boiler.

b

C43 flue systems must not be a 'pressurised system'

but act under natural draught principles

b

C43 type flue systems must have their own

condensate drain fitted and not allow condensate to

mix into other appliances

L

B

A

1

2

3

4

5

Key

1 Pressure balancing system

2 Air-inlet pipe

3 Collector pipe

4 boiler

5 Inspection hatch

A final storey

b Ground floor

Type

Max length (L)

Ø 60/100

10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.