Maintenance, 17 draining, 18 servicing – Glow-worm Ultracom2 35 Store User Manual

Page 44

Advertising
background image

0020112185_PROTO_13 - 01/11 - Glow-worm

- 42 -

• Compare the value measured with the values indicated in the

table below.

Gas adjustment

G20

G31

CO

2

case ON

9 ± 0.2 %

10.1 ± 0.2 %

CO

2

case OFF

9.2 ± 0.3 %

10.3 ± 0.3 %

i

Safe combustion can only be verified by measuring

CO/CO

2

ratio. This must not exceed the value shown

in the table under the section "Maximum Rate and

Adjustment".

16.1.3

Restarting

• Replace the cap

• Replace the appliance front panel.

Note: following the replacement of the front panel, the CO

2

value

will change: you can check that the value "case on" is correct by

the values in the previous table.

2

1

Key

1 Gas change label location

2 Data label location

• Firmly attach the gas replacement label to the appliance in the

corresponding location (1) on the electrical box.

• Depending on the gas replacement label, tick the type of gas

used on the sticker.

16.2 Restart - re-check commissioning

• Before putting the appliance into operation, follow the

instructions within the chapter Specific adjustment.

17 Draining

17.1 Heating circuit

1

Key

1 Heating drain tap

• Open the heating drain tap (1) located under the boiler.

• Make an air intake by, for example, opening a bleed in the

installation.

• To just drain the heating circuit water contained within the

appliance, first close the heating outlet and return valves.

17.2 Domestic Hot water circuit

• Drain the

d

omestic Hot Water circuit by closing the cold-water

isolation valve on the wall mounting jig.

• Open one or more hot water taps to drain the hot water circuit.

18 Servicing

• To ensure the continued efficient and safe operation of the

boiler it is recommended that it is checked and serviced as

necessary at regular intervals.

The frequency of servicing will depend upon the particular

installation conditions and usage.

If this appliance is installed in a rented property there is a duty of

care imposed on the owner of the property by the current issue of

the Gas Safety (Installation and Use) Regulations, Section 35.

MAINTENANCE