13 Specific adjustment

13.1 Heating circuit adjustment

It may be necessary to adjust the by-pass to the design of the

system. The boiler is delivered pre-set open 1/2 turn (1).

1

Key

1 Screw for by-pass

• Depending on the design of the system the by-pass may need

further adjustment. It is adjusted clockwise to close and anti-

clockwise to open. This should be balanced to ensure that it

operates if the pump output is adjusted.

Output/pressure curve Ultracom

2

35 Store

60
50
40
30
20
10

0

500

1000

1500

B

1

2

Key

A Available pressure between heating flow and return (kPa)

b Heating circuit flow rate (l/h)

1 Speed min

2 Speed max

13.2 Appliance technical settings and parameter

list

The access to the boilers technical data allows you to adjust the

boiler to the exact system requirements.

Note: the heating power decrease has no effect on the domestic

hot water power.

13.2.1

Installation settings

• Press

the menu button for 7 seconds

to access the

configuration menu. The screen displays "0".

• Press

the

button 4 times

for mode. The screen displays

"96". This is the installer's password.

• Press

to validate. The screen displays the parameter

"00" and its value "XX”.

• Press or button

of mode to access the parameter to

modify.

• Press or button

of the

h

eating temperature controls to

modify the value of the parameter.

• Repeat the past two

stages

for each parameter that needs to

be modified.

• Press

the

button for more than 3 seconds

to exit the

installer

menu.

INSTALLATION