Maintenance – Glow-worm Ultracom2 35 Store User Manual

Page 55

Advertising
background image

0020112185_PROTO_13 - 01/11 - Glow-worm

- 53 -

Key

1 Safety Discharge Valve

2 Safety Discharge Valve discharge pipe

3 Domestic hot water pump head connector

4 Domestic hot water pump head

5 Domestic hot water pump head nut

6 Domestic hot water pump housing

7 "foaming" filter retaining clip

8 "foaming" filter

9 Heating pump head connector

10 Heating pump head

11 Heating pump head retaining srcews

12 Heating pump head earth lead

13 Automatic air vent retaining clip

14 flexible 3WV / tank

15 Heating pump housing

16 Automatic air vent

17 Heating return pipe retaining clip

18 Heating return pipe

19 Heating expansion vessel pipe

20 Hot water temperature sensor

21 flexible 3WV / tank

22 Low water pressure sensor connector

23 Low water pressure sensor

24 Low water pressure sensor retaining clip

25 Hot water heat exchanger output temperature sensor

26 Domestic hot water pump housing retaining clip

27 flexible 3WV / tank

28 Pipe

29 Plate-to-plate heat exchanger

30 Heating flow pipe

31 bypass screw

32 Plate-to-plate heat exchanger retaining screws

33 bypass retaining clip

34 flexible 3WV / tank retaining clip

35 Three-way valve

36 Three-way valve electrical plug

37 Three-way valve retaining screws

38 flexible 3WV / tank retaining clip

39 Safety Discharge Valve discharge retaining clip

19.4.1

Heating pump (head only)

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Disconnect the electrical plug (9) from the main board.

• Disconnect the electrical plug (12) from the pump head.

• Remove the four cap head screws (11).

• Carefully remove the pump head (10) together with cable.

Do not strain cable.

• Reconnect wiring to new pump head and fit cover.

• Fit the new pump head by repeating the operations in reverse.

19.4.2

Safety discharge valve

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Undo the safety discharge valve union and remove from the

pipework (2).

• Remove the securing clip (39) and withdraw the safety

discharge valve (1).

• Fit new ‘O’ ring. Refill, vent and pressurise the boiler.

19.4.3

Automatic air vent

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Remove the retaining clip (13).

• Remove the automatic air vent (16).

• Fit the new automatic air vent and ‘O’ ring ensuring the vent

cap is left loose.

• Refill, vent and pressurise the boiler.

19.4.4

Low water pressure sensor

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Disconnect the electrical lead (22).

• Remove the retaining clip (24), remove the low water pressure

sensor (23).

• Fit the new low water pressure sensor.

• Refill vent and pressurise the boiler.

19.4.5

bypass

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Remove the retaining clip (33) to remove the bypass screw (31).

• After replacing the bypass, refill, vent and pressurise the

boiler.

19.4.6

Three way valve

• Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

• Disconnect the electrical plug (36).

• Remove the two retaining screws (37).

• Remove the three way valve (35).

• Fit new three way valve assembly.

• Refill, vent and pressurise the boiler.

19.4.7

"foaming" filter

• Drain the boiler heating and domestic hot water circuits as

described in the appropriate chapter "Draining".

• Remove the filter retaining clip (7) located under the pump.

• Relieve the "foaming" filter (8).

• Refill vent and pressurise the boiler.

MAINTENANCE