Installation – Glow-worm Ultracom2 35 Store User Manual

Page 34

Advertising
background image

0020112185_PROTO_13 - 01/11 - Glow-worm

- 32 -

Code Parameter

Unit

Description

factory

setting

Modifiable

parameter

d.00 Maximum heating power

kW

Choose a value:

8 to 30 kW

30

yes

d.01 Pump over-run time - heating

min. Choose a value between 2 and 60.

5

yes

d.02 Blocking time for burner in heating

mode (anti-cycle time)

min.

To prevent the burner frequently switching on and off,

the reactivation of the burner is electronically blocked for a period

that is determined each time the burner stops. The burner blocking

time can be adapted to the usage conditions for the heating

installation and depends on the temperature that is set for heating:

- at 80°C, the period is fixed (2 minutes)

- at 10°C, the period is adjustable: choose a value between 2 and 60

minutes.

20

yes

d.03 Plate exchanger inlet temperature.

°C

Display of the plate exchanger inlet temperature on the short circuit

-

no

d.04 Temperature of water in the tank

°C

Display tank water temperature.

-

no

yes

Pump function

-

Mode:

0 = With the burner

1 = Continuous with ambient temperature

2 = Continuous

1

yes

yes

Speed of the pump

-

Functioning mode:

0 = Automatic: maximum speed when the burner is switched on

1 = Minimum speed

2 = Automatic: automatic speed when the burner is switched on

3 = Maximum speed

2

yes

yes

Maximum temperature setting for

domestic hot water

°C

The recommended maximum temperature setting for domestic hot

water is 60°C. Choose a value suitable for your needs.

60

yes

The following 2 menus are displayed if an option card (not supplied) is installed on the appliance.

d.27 Function relay 1

-

Attributing a function to relay 1 of the option card:

1 = Domestic hot water circulation pump

2 = auxiliary heating pump

3 = Reservoir loading pump

4 = smoke valve / chimney extractor

5 = external gas valve

6 = external error message

1

yes

d.28 Function relay 2

-

Attributing a function to relay 2 of the option card:

1 = Domestic hot water circulation pump

2 = auxiliary heating pump

3 = Reservoir loading pump

4 = smoke valve / chimney extractor

5 = external gas valve

6 = external error message

2

yes

The following menu displays automatically if an automatic fill kit is installed on the appliance.

d.31 Refill method

-

Operating mode:

0 = Manual

1 = Semi-automatic

2 = Automatic

0 or 2

-

d.34 Speed of fan

tr/

min.

Fan speed is displayed between 0 and 99.

Multiply the displayed value by 100.

-

no

d.35 Position of 3-way valve

-

0 = Heating

100 = Hot water

-

no

d.36 Domestic hot water flow

l/

min. Display domestic hot water flow.

-

no

The following menu is displayed if a solar system (not supplied) is connected to the appliance

d.39 Solar circuit water temperature

°C

Displays the water temperature measured by the sensor located

upstream of the mixer.

-

no

d.40 Heating flow temperature

°C

Display the heating flow temperature.

-

no

d.41 Heating return temperature

°C

Display the heating return temperature.

-

no

INSTALLATION