Confirm, confirms and saves in the memory the values programmed on the screen

�

Back, returns to the home screen of the setup menu

figure 113

.

Main Menu, back to the main menu,

figure 25

.

Use the keys

and

to select the different options.

To confirm the selection, press the key

.

If no key is pressed for 5 minutes, the display screen changes automatically to the default

screen, which displays the voltage measurement of 4 parameters.

● When programming the

maximum value above which the relay is activated:

The units and maximum and minimum values of the variables to program are shown in

Table 22

.

NB: The maximum value must be greater than the minimum value programmed.

,

...

,

,

The ten possible digits to program

�

Delete character, deletes the selected character

�

Delete parameter, deletes the characters of the selected parameter.

Previous, selects the previous parameter

�

Next, selects the next parameter

�

Confirm, confirms and saves in the memory the values programmed on the screen

�

Back, returns to the home screen of the setup menu

figure 113

.

Main Menu, back to the main menu,

figure 25

.

Use the keys

and

to select the different options.

To confirm the selection, press the key

.

If no key is pressed for 5 minutes, the display screen changes automatically to the default

screen, which displays the voltage measurement of 4 parameters.

Table 22: Units and maximum and minimum values of the programming variables of the digital outputs�

Variable

Units

Maximum

Minimum

Phase-Neutral Voltage

V

1000.00 * voltage ratio

(1)

0

Phase-Phase Voltage

V

Neutral Voltage

V

Current

A

10.000 *current ratio

(2)

0

Neutral Current

A

Frequency

Hz

70.00

40.00

149

Instruction Manual

CVM-B100 - CVM-B150