Modbus communications – CIRCUTOR CVM-B Series User Manual

Page 293

Advertising
background image

Maximum value: 250.

Minimum value:

1

.

Use the

and

buttons to select the different options.

To confirm the selection, press the

button.

If no button is pressed for 5 minutes, the display screen changes automatically to the default

screen, which displays the voltage measurement of 4 parameters.

● When programming the

transmission speed, Baud rate:

,

...

Possible transmission speeds

:1200, 2400, 4800 o 9600�

Previous, selects the previous parameter

�

Next, selects the next parameter

�

Confirm, confirms and saves the values programmed on the screen in the

memory

�

Back, returns to the main configuration screen of the expansion modules menu.

Main Menu, returns to the main menu,

figure 25

.

Use the

and

buttons to select the different options.

To confirm the selection, press the

button.

If no button is pressed for 5 minutes, the display screen changes automatically to the default

screen, which displays the voltage measurement of 4 parameters.

7�8�4�- MODBUS COMMUNICATIONS

The following functions are implemented for this variable:

function 0x04: reading logs.

function 0x10: Writing multiple logs.

Table 152:Modbus memory map: MBus communications module

Configuration of the MBus parameters

Configuration variable

Address

Valid data margin

Default value

Primary address

EE48

1 - 250

1

Baud rate

EE49

2: 1200 - 3: 2400 -

4: 4800 - 5: 9600

5

Note: The 2 logs can be read separately, but they must be written at the same time (as a

group). Otherwise, the system will reply with an error.

293

Instruction Manual

CVM-B100 - CVM-B150