Figure 63, Equation 8 – Basler Electric BE1-11g User Manual

Page 111

Advertising
background image

9424200994 Rev N

99

π΄π‘π‘‘π‘’π‘Žπ‘™ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝐿𝑒𝑣𝑒𝑙 =

𝑆𝑒𝑛𝑠𝑖𝑛𝑔 π‘‰π‘œπ‘™π‘‘π‘Žπ‘”π‘’ 𝐿𝑒𝑣𝑒𝑙

π‘…π‘’π‘ π‘‘π‘Ÿπ‘Žπ‘–π‘›π‘‘ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝑆𝑒𝑑𝑑𝑖𝑛𝑔 Γ— 51 π‘ƒβ„Žπ‘Žπ‘ π‘’ π‘ƒπ‘–π‘π‘˜π‘’π‘ 𝑆𝑒𝑑𝑑𝑖𝑛𝑔

Equation 8. Restraint Pickup Level

Figure 63. 51 Phase Pickup Level Compensation

Phase VT Configuration

The 51/27R function can be set to monitor either Vpp or Vpn depending upon the Phase VT Connection
settings. See the

Configuration

chapter for details on how to set the phase VT connections. Table 34

shows which voltage measurements are used by each 51 element for each possible phase VT connection
and 51/27 voltage monitoring mode setting.

Table 34. Phase VT Connection Cross Reference

Phase VT Connection

51/27 Mode

51A

51B

51C

4W

Vpp

Vab

Vbc

Vca

4W

Vpn

Van

Vbn

Vcn

3W

Vpp

Vab

Vbc

Vca

AN

Vpn

Van

n/a

n/a

BN

Vpn

n/a

Vbn

n/a

CN

Vpn

n/a

n/a

Vcn

AB

Vpp

Vab

n/a

n/a

BC

Vpp

n/a

Vbc

n/a

CA

Vpp

n/a

n/a

Vca


Note

For single-phase sensing, the unmonitored phase is not restrained or
controlled. These phases are marked in the table by n/a (not
applicable).

BE1-11g

Inverse Overcurrent (51) Protection

Advertising