552

9424200994 Rev N

Reactive Power
5 Ampere CT Range ................................................. –7,500 var to +7,500 var
1 Ampere CT Range ................................................. –1,500 var to +1,500 var
Accuracy....................................................................

±1% at zero power factor

Energy Data Reporting

5 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
1 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
Units of Measure ....................................................... kilo
Rollover Value of Registers....................................... 1,000,000,000 kWhr or kvarhr
Accuracy....................................................................

±1% at unity power factor

21 - Distance Protection

Diameter

Setting Range ........................................................ 0 to 500

5 Ampere CT Accuracy ..........................................

±3% or ±0.2 Ω, whichever is greater from 0 to 100 Ω

1 Ampere CT Accuracy ..........................................

±3% or ±0.2 Ω, whichever is greater from 0 to 500 Ω

Time Delay
Setting Range ........................................................ 0 to 300,000 ms
Accuracy.................................................................

±0.5% or ±2 cycles, whichever is greater

Torque Angle
Setting Range ........................................................ 0 to 90 degrees
Accuracy.................................................................

±1 degree

Offset
Setting Range ........................................................

–500 to 500 Ω

5 Ampere CT Accuracy ..........................................

±3% or ±0.2 Ω, whichever is greater from –100 to 100 Ω

1 Ampere CT Accuracy ..........................................

±3% or ±0.2 Ω, whichever is greater from –500 to 500 Ω

24 - Overexcitation Protection

Inverse Time
Curve Exponent ........................................................ 0.5, 1, or 2

Pickup

Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................

±2% or ±0.05 V/Hz, whichever is greater

Dropout/Pickup Ratio ................................................ 98%

±1%

Time Dial

Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................

±5% or ±3 cycles, whichever is greater

Reset Dial

Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................

±5% or ±3 cycles, whichever is greater

Definite Time 1 and 2

Pickup

Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................

±2% or ±0.05 V/Hz, whichever is greater

Time Delay

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±3 cycles, whichever is greater