Energy data reporting, 21 - distance protection, 24 - overexcitation protection – Basler Electric BE1-11g User Manual
Page 564

552
9424200994 Rev N
Reactive Power
5 Ampere CT Range ................................................. –7,500 var to +7,500 var
1 Ampere CT Range ................................................. –1,500 var to +1,500 var
Accuracy....................................................................
±1% at zero power factor
Energy Data Reporting
5 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
1 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
Units of Measure ....................................................... kilo
Rollover Value of Registers....................................... 1,000,000,000 kWhr or kvarhr
Accuracy....................................................................
±1% at unity power factor
21 - Distance Protection
Diameter
Setting Range ........................................................ 0 to 500
Ω
5 Ampere CT Accuracy ..........................................
±3% or ±0.2 Ω, whichever is greater from 0 to 100 Ω
1 Ampere CT Accuracy ..........................................
±3% or ±0.2 Ω, whichever is greater from 0 to 500 Ω
Time Delay
Setting Range ........................................................ 0 to 300,000 ms
Accuracy.................................................................
±0.5% or ±2 cycles, whichever is greater
Torque Angle
Setting Range ........................................................ 0 to 90 degrees
Accuracy.................................................................
±1 degree
Offset
Setting Range ........................................................
–500 to 500 Ω
5 Ampere CT Accuracy ..........................................
±3% or ±0.2 Ω, whichever is greater from –100 to 100 Ω
1 Ampere CT Accuracy ..........................................
±3% or ±0.2 Ω, whichever is greater from –500 to 500 Ω
24 - Overexcitation Protection
Inverse Time
Curve Exponent ........................................................ 0.5, 1, or 2
Pickup
Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................
±2% or ±0.05 V/Hz, whichever is greater
Dropout/Pickup Ratio ................................................ 98%
±1%
Time Dial
Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................
±5% or ±3 cycles, whichever is greater
Reset Dial
Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................
±5% or ±3 cycles, whichever is greater
Definite Time 1 and 2
Pickup
Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................
±2% or ±0.05 V/Hz, whichever is greater
Time Delay
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±1.5% or ±3 cycles, whichever is greater
Specifications