Timing verification (vx fundamental mode) – Basler Electric BE1-11g User Manual

Page 413

Advertising
background image

9424200994 Rev N

401

Setting

Value

BESTCOMSPlus Screen

Description

Inhibit Level

10 V

Protection, Voltage,
Undervoltage (27X-1)

Sets inhibit level to 10 V

Timing Mode

Definite

Protection, Voltage,
Undervoltage (27X-1)

Selects definite timings

27X-1 AUX

Enabled

Target Configuration, Targets

Enables Vx Fundamental target
for 27X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 283.

Blocking is disabled.

OUT1 closes for 27X-1 Trip.

OUT2 closes for 27X-1 Pickup.

Fault recording is enabled.

Figure 283. BESTlogicPlus Settings (Vx Fundamental Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 149 to the BE1-11g.

Table 149. Pickup Test Settings (Vx Fundamental Mode)

Pickup Setting

Time Delay

115 V

50 ms

65 V

50 ms

20 V

50 ms

Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 283).

Step 5: Connect and apply a 120 Vac, single-phase voltage source to the Vx input, terminals C17

(polarity) and C18 (non-polarity).

Step 6: Slowly decrease the voltage until OUT2 closes and record the pickup. Verify that there is a 27X-

1-AUX target on the front-panel display. Slowly increase the voltage until OUT2 opens and
record the reset. Reset the target.

Step 7: Verify the pickup and reset accuracy at 70 Vac for a pickup setting of 65 V and 25 Vac for a

pickup setting of 20 V as listed in Table 149. Record the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 27X-2, 27X-3, and 27X-4.

Timing Verification (Vx Fundamental Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 150 to the BE1-11g for settings group 0.

BE1-11g

Auxiliary Undervoltage (27X) Test