Operational settings – Basler Electric BE1-11g User Manual

Page 132

Advertising
background image

120

9424200994 Rev N

Operational Settings

Neutral current differential element operational settings are configured on the Neutral Current Differential
(87N) settings screen (Figure 75) in BESTCOMSPlus. Setting ranges and defaults are summarized in
Table 43.

Figure 75. Neutral Current Differential Settings Screen

Table 43. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Iop Minimum

0 or 0.1 to 5 (5A CTs)

0 or 0.02 to 1 (1A CTs)

0.01

amps

0

Time Delay

0 to 60,000

varies

milliseconds

0

Overcorrection Coefficient

1 to 1.3

0.01

units

1.10

CT Flip

Yes or No

n/a

n/a

Yes

CT Source

CT1, IG1 or CT2, IG2

n/a

n/a

CT1, IG1

Transient Delay Time

0 to 10,000

varies

milliseconds

0

Neutral Current Differential (87N) Protection

BE1-11g