Functional test report - anticipatory, Voltage monitor functional test procedure – Basler Electric BE1-11g User Manual

Page 535

Advertising
background image

9424200994 Rev N

523

Functional Test Report - Anticipatory

ΔV Accuracy = ±2% or ±1 V, whichever is greater.

Slip Freq Accuracy =

±0.01 Hz

Breaker Close Time Accuracy = 0.5% or

±2 cycles, whichever is greater.

Pulse Width/Interval Accuracy = 0.5% or

±2 cycles, whichever is greater.

Test

Setting

Low

Actual

High

Pass/Fail

ΔV Increasing

15% (79.67 V)

78.67 V

80.67 V

P / F

ΔV Decreasing

15% (58.89 V)

57.89 V

59.89 V

P / F

Slip Freq

Increasing

0.5 Hz

60.49 Hz

60.51 Hz

P / F

Slip Freq

Decreasing

0.5 Hz

59.49 Hz

59.51 Hz

P / F

Volt Pulse Width

Increasing

5.0 s

4.977 s

5.033 s

P / F

Volt Pulse Width

Decreasing

5.0 s

4.977 s

5.033 s

P / F

Volt Pulse

Interval

Increasing

10.0 s

9.950 s

10.050 s

P / F

Volt Pulse

Interval

Decreasing

10.0 s

9.950 s

10.050 s

P / F

Freq Pulse

Width Increasing

10.0 s

9.950

10.050 s

P / F

Freq Pulse

Width

Decreasing

10.0 s

9.950 s

10.050 s

P / F

Freq Pulse

Interval

Increasing

5.0 s

4.977 s

5.033 s

P / F

Freq Pulse

Interval

Decreasing

5.0 s

4.977 s

5.033 s

P / F

Voltage Monitor Functional Test Procedure

VTP and VTX Live Voltage, Dead Voltage Pickup Test (25A Voltage Monitor)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 237 to the BE1-11g. Reset all

targets.

Table 237. Operational Settings (25)

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1.

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection
to 4W-Y.

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral.

Aux VT Ratio

1

System Parameters, Sensing

Sets auxiliary VT ratio to 1.

BE1-11g

Synchronizer (25A) Test