Functional test report - anticipatory, Voltage monitor functional test procedure – Basler Electric BE1-11g User Manual
Page 535

9424200994 Rev N
523
Functional Test Report - Anticipatory
ΔV Accuracy = ±2% or ±1 V, whichever is greater.
Slip Freq Accuracy =
±0.01 Hz
Breaker Close Time Accuracy = 0.5% or
±2 cycles, whichever is greater.
Pulse Width/Interval Accuracy = 0.5% or
±2 cycles, whichever is greater.
Test
Setting
Low
Actual
High
Pass/Fail
ΔV Increasing
15% (79.67 V)
78.67 V
80.67 V
P / F
ΔV Decreasing
15% (58.89 V)
57.89 V
59.89 V
P / F
Slip Freq
Increasing
0.5 Hz
60.49 Hz
60.51 Hz
P / F
Slip Freq
Decreasing
0.5 Hz
59.49 Hz
59.51 Hz
P / F
Volt Pulse Width
Increasing
5.0 s
4.977 s
5.033 s
P / F
Volt Pulse Width
Decreasing
5.0 s
4.977 s
5.033 s
P / F
Volt Pulse
Interval
Increasing
10.0 s
9.950 s
10.050 s
P / F
Volt Pulse
Interval
Decreasing
10.0 s
9.950 s
10.050 s
P / F
Freq Pulse
Width Increasing
10.0 s
9.950
10.050 s
P / F
Freq Pulse
Width
Decreasing
10.0 s
9.950 s
10.050 s
P / F
Freq Pulse
Interval
Increasing
5.0 s
4.977 s
5.033 s
P / F
Freq Pulse
Interval
Decreasing
5.0 s
4.977 s
5.033 s
P / F
Voltage Monitor Functional Test Procedure
VTP and VTX Live Voltage, Dead Voltage Pickup Test (25A Voltage Monitor)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 237 to the BE1-11g. Reset all
targets.
Table 237. Operational Settings (25)
Setting
Value
BESTCOMSPlus Screen
Description
Phase VT Ratio
1
System Parameters, Sensing
Transformers
Sets phase VT ratio to 1.
Phase VT
Connection
4W-Y
System Parameters, Sensing
Transformers
Sets phase VT connection
to 4W-Y.
27/59 Mode
PN
System Parameters, Sensing
Transformers
Sets 27/59 mode to phase-
neutral.
Aux VT Ratio
1
System Parameters, Sensing
Sets auxiliary VT ratio to 1.
BE1-11g
Synchronizer (25A) Test