Breaker Monitoring

Breaker monitoring helps manage equipment inspection and maintenance expenses by providing
extensive monitoring and alarms for the circuit breaker. Breaker monitoring functions include breaker
status and operations counter reporting, fault current interruption duty monitoring and trip-speed
monitoring. Each function can be set up as a programmable alarm. The

Alarms

chapter has more

information about the use of programmable alarms. The breaker trip circuit voltage and continuity monitor
is a related function and is described in the

Trip Circuit Monitor (52TCM)

chapter.

Breaker Status Reporting

The breaker status monitoring function monitors the position of the breaker for reporting purposes.
Opening breaker strokes are also counted and recorded in the breaker operations counter register. Circuit
breaker status is also used by the 50BF function, the 60FL function, the 25A function, and the 52TCM
function. The breaker status logic block is shown in Figure 148.

Figure 148. Breaker Status Logic Block

BESTlogic

Plus Settings for Breaker Status

Since the BE1-11g is completely programmable, it is necessary to program which logic variable will
monitor breaker status. Breaker status is programmed using BESTCOMSPlus

®. Use the Settings Explorer

to open the BESTlogicPlus Programmable Logic tree branch and select the Breaker Status logic block
from the list of Elements. Use the drag and drop method to connect a variable or group of variables to the
input. Refer to the

BESTlogicPlus

chapter for more information on setting BESTlogicPlus programmable

logic.

Table 80 summarizes the BESTlogicPlus settings for Breaker Status.

Table 80. BESTlogicPlus Settings for Breaker Status

Setting

Range/Purpose

Default

Breaker Status

True when the breaker is closed (e.g., 52a logic).

0

Retrieving Breaker Status and Operation Counter Information

BESTCOMSPlus Navigation Path: Metering Explorer, Status, Breaker Status

HMI Navigation Path: Metering Explorer, Status, Breaker Status

Breaker status can be viewed through BESTCOMSPlus, the front-panel display, and the web page
interface.

To view breaker status using BESTCOMSPlus, use the Metering Explorer to open the Status, Breaker
Status screen shown in Figure 149. To view breaker status at the front-panel display, navigate to
Metering Explorer, Status, Breaker Status.

Figure 149. Breaker Status Screen

The number of breaker operations can be read at the front-panel display. The counter value can be
adjusted using the Edit key. This allows the BE1-11g counter value to be matched to an existing
mechanical cyclometer on a breaker mechanism. Write access to the reports functions must be gained to