Basler Electric BE1-11g User Manual
Page 461

9424200994 Rev N
449
Setting
Value
BESTCOMSPlus Screen
Description
Element
Mode
IA
Protection, Current, Instantaneous
Overcurrent (50-1)
Enables 50-1 function
Pickup
2 A
Protection, Current, Instantaneous
Overcurrent (50-1)
Sets pickup to 2 A
Source
CT Circuit 1
Protection, Current, Instantaneous
Overcurrent (50-1)
Selects CT circuit 1 as the
source
Step 8: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 301.
•
50BF Blocking is disabled.
•
50BFI is initiated with 50-1 Trip.
•
52BFI is disabled.
•
OUT1 closes for 50BF Trip.
•
OUT2 closes for 50BF ReTrip.
•
OUT3 closes when minor alarm is true. (Minor Alarm = Breaker Fail)
•
Fault recording is enabled.
•
Breaker Status is disabled.
•
50-1 Blocking is disabled.
Figure 301. BESTlogicPlus Settings (BFI50 Current Supervised BE1-11g Trip Initiate)
Step 9: Verify the BF time delay by applying pickup current (above 2 A) to phase A for at least 100 ms.
A 50BF Trip should occur. Use BESTCOMSPlus to retrieve an SER report and verify that a
50BF Trip was logged 100 milliseconds
±0.5% (1¼ cycles maximum for currents ≥ 5 times the
pickup setting. 1¾ cycles maximum for a current of 2 times pickup. Two cycles maximum for a
current of 1.05 times the pickup setting) after application of pickup current.
Step 10: (Optional.) Raise 50-1 Pickup setting to 10 amps and apply nominal current to the BE1-11g.
Note that OUT1 and OUT2 do not operate. No initiate prevents operation of the breaker failure
function, blocking the breaker fail logic.
Step 11: Verify the Control Time function by using BESTCOMSPlus to send the settings in Table 195 to
the BE1-11g.
Step 12: Connect a current source to terminals D1 and D2 (A-phase). Apply nominal current to the
BE1-11g and note operation of OUT3 and no operation of OUT1 and OUT2. To verify control
time, apply nominal current and start the test set timer. Use OUT3 to stop the timer. Record the
result.
BE1-11g
Breaker Fail (50BF) Test