Pickup verification (mho characteristic 2), Timing verification (mho characteristic 1), Timing verification (mho characteristic 2) – Basler Electric BE1-11g User Manual

Page 520

Advertising
background image

508

9424200994 Rev N

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

10.0 V (5

Ω)

9.70 V

10.3 V

P / F

6

8.00 V

7.92 V

8.08 V

P / F

Pickup Verification (mho Characteristic 2)

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

5

10.0 V (5

Ω)

9.70 V

10.3 V

P / F

6

8.00 V

7.92 V

8.08 V

P / F

Timing Verification (mho Characteristic 1)

Time Delay Range = 0 to 300,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,967 ms

2,033 ms

P / F

5

1,000 ms

967 ms

1,033 ms

P / F

Timing Verification (mho Characteristic 2)

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,967 ms

2,033 ms

P / F

5

1,000 ms

967 ms

1,033 ms

P / F


Loss of Excitation – Impedance Based (40Z) Test