Operational settings – Basler Electric BE1-11g User Manual

Page 69

Advertising
background image

9424200994 Rev N

57

Operational Settings

Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings
screen (Figure 45) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 15.

Figure 45. Phase Undervoltage Settings Screen

Table 15. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled,

One of Three,
Two of Three,

or Three of Three

n/a

n/a

Disabled

Pickup

0 or 1 to 300

0.1

volts

0

Inhibit Level

0 or 1 to 300

0.1

volts

0

Timing Mode

Definite or Inverse

n/a

n/a

Definite

Time Delay (Definite Timing)

50 to 600,000

varies

milliseconds

50

Time Dial (Inverse Timing)

0 to 9.9

0.1

units

0

BE1-11g

Phase Undervoltage (27P) Protection