Transformers

Aux VT
Connection

AN

System Parameters, Sensing
Transformers

Sets auxiliary VT
connection to AN.

Nominal Phase
Voltage

100 V

System Parameters, Power
System

Sets nominal phase voltage
to 100 V.

Nominal Aux
Voltage

100 V

System Parameters, Power
System

Sets nominal auxiliary
voltage to 100 V.

Element Mode

PLL or
Anticipatory

Control, Synchronizer (25A)

Enables the 25A function.

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in

Figure 317.

•

Blocking is disabled.

•

25A is initiated.

•

OUT7 closes for voltage monitor criteria met.

•

Event recording is enabled.

Figure 317. BESTlogicPlus Settings 3 (25A)

Step 3: Use BESTCOMSPlus to open the Control, Synchronizer (25A) screen and send the test settings

in Table 238 to the BE1-11g.

Table 238. Time Pickup Test Settings (25VM)

Setting

Value

Description

25 Voltage Monitor Live
Voltage

90%

Sets live voltage to 90 V (90% of nominal, nominal
= 100 V).

25 Voltage Monitor
Dead Voltage

55%

Sets dead voltage to 55 V (55% of nominal, nominal
= 100 V).

25 Voltage Monitoring
Drop Out Delay

0

Sets drop out delay to 0.

25 Voltage Monitor
Logic

Check boxes as
shown in Figure 318.

Enable: Dead Line/Dead Aux, Dead Line/Live Aux,
Live Line/Dead Aux.

Synchronizer (25A) Test