Table 101. Default Function Block Logic

Function

Purpose

BESTlogic

Plus

Inputs

50-1

Used for instantaneous phase overcurrent protection.

0

50-2

Used for instantaneous neutral overcurrent protection.

0

50-3

Used for instantaneous negative-sequence overcurrent protection.

0

51-1

Used for timed phase overcurrent protection.

0

51-2

Used for timed neutral overcurrent protection.

0

51-3

Used for timed negative-sequence overcurrent protection.

0

FAULT TRIGGER

Trip

Trip Bus

Picked Up

Pickup Bus

Logic

0

Table 102. Default Output Logic

Output

Purpose

Description

Label

State Labels

Energized

De-

Energized

OUTA

Alarm Output Contact.

Alarm contact closes/opens (refer
to style number) automatically
when relay trouble alarm occurs.

Output

Alarm

On

Off

OUT1

Breaker Trip Output.

Contact closes when protective
trip expression is TRUE.

Output

1

On

Off

OUT2

Instantaneous Phase
OC Auxiliary Contact.

Contact closes when
instantaneous overcurrent (50-1)
trip occurs.

Output

2

On

Off

OUT3

Timed Phase OC
Auxiliary Contact.

Contact closes when inverse
overcurrent (51-1) trip occurs.

Output

3

On

Off

OUT4

Instantaneous Neutral
and Negative-
Sequence OC.

Contact closes when
instantaneous overcurrent (50-2
or 50-3) trip occurs.

Output

4

On

Off

OUT5

Timed Neutral and
Negative-Sequence
OC.

Contact closes when inverse
overcurrent (51-2 or 51-3) trip
occurs.

Output

5

On

Off

BE1-11g

BESTlogic

Plus