How can i check the version number of my be1-11g, Features, Communications – Basler Electric BE1-11g User Manual

Page 558: Is the irig signal modulated or demodulated

Advertising
background image

546

9424200994 Rev N

How can I check the version number of my BE1-11g?

The application version can be found in four different ways: One, on the Settings > General Settings >
Device Information screen of the front-panel display. Two, on the Settings Explorer, General Settings,
Device Info screen of BESTCOMSPlus. Three, on the Status (home) page of the web page interface.
Four, on the Metering Explorer, Device Info screen of BESTCOMSPlus.

Features

How many overcurrent elements does the BE1-11g have available?

The BE1-11g has six instantaneous overcurrent and seven inverse overcurrent elements. Like any
element, each element can be assigned to any output for building logic equations.

Communications

Is the IRIG signal modulated or demodulated?

The BE1-11g accepts an IRIG-B signal that is demodulated (dc level-shifted digital signal). See the

Specifications

chapter for additional information.

Frequently Asked Questions (FAQ)