Functional test report, Pickup verification, Dropout verified in previous steps – Basler Electric BE1-11g User Manual

Page 524: Timing verification

Advertising
background image

512

9424200994 Rev N

Step 7: Set the voltage input angles to A

∠180°, B∠60°, C∠300°. Increase the voltage until OUT3

reopens and record the time between when OUT3 opens and OUT1 opens. This should be
6,000 ms

±33.3 ms.

Step 8: (Optional.) Repeat steps 1 through 7 for settings groups 1, 2, and 3.

Functional Test Report

Pickup Verification

MHO Characteristic Pickup Accuracy =

±2% or 0.1 Ω, whichever is greater.

Blinder Pickup Accuracy =

±2% or 0.1 Ω, whichever is greater.

MHO Dropout =

±5%

Blinder Dropout =

±1%

Step

Pickup

Point

Low

Actual

Pickup

High

Low

Actual

Dropout

High

Pass/Fail

6/7 – A-phase

34.64 V

33.95 V

35.33 V

35.64 V

37.10 V

P / F

8/9 – A-phase

–73.22°

–73.57°

–72.88°

–73.40°

–72.70°

P / F

10 – A-phase

–106.8°

–107.1°

–106.4°

N/A

*

N/A

*

N/A

*

P / F

11 – A-phase

34.64 V

33.95 V

35.33 V

N/A

*

N/A

*

N/A

*

P / F

* Dropout verified in previous steps.

Timing Verification

Time Delay Range = 0 to 10,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

5 – Traverse

1,000 ms

967 ms

1,033 ms

P / F

6 – Trip

1,000 ms

967 ms

1,033 ms

P / F

7 – Reset

*

6,000 ms

5,967 ms

6,033 ms

P / F

* The reset time delay is programmed at the factory for 6,000ms and cannot be changed.

Out of Step (78OOS) Test

BE1-11g

Advertising