27p - phase undervoltage protection – Basler Electric BE1-11g User Manual

Page 584

Advertising
background image

572

9424200994 Rev N

Voltage Controller

Volt Pulse Width

Setting Range ........................................................... 0.1 to 5 seconds
Accuracy....................................................................

±1% or ±3 cycles, whichever is greater

Volt Pulse Interval

Setting Range ........................................................... 0.2 to 10 seconds
Accuracy....................................................................

±1% or ±3 cycles, whichever is greater

Frequency Controller

Frequency Pulse Width

Setting Range ........................................................... 0 to 99.9 seconds
Accuracy....................................................................

±1% or ±3 cycles, whichever is greater

Frequency Pulse Interval

Setting Range ........................................................... 0 to 99.9 seconds
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

Sensing Setup
Angle Compensation Setting Range ......................... 0 to 359.9

°

Voltage Monitoring

Live/Dead Voltage

Setting Range ........................................................... 0 to 90%
Accuracy....................................................................

±2%

Drop Out Delay

Setting Range ........................................................... 50 to 60,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

27P - Phase Undervoltage Protection

Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio .................................................... 102%

±1%

Inhibit Level
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Inhibit Ratio ..................................................... 102%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±8% or ±4 cycles, whichever is greater
Refer to the

Time Curve Characteristics

chapter for

information on available timing curves.

Specifications - 25 Hz Operation

BE1-11g