Basler Electric BE1-11g User Manual

Page 518

Advertising
background image

506

9424200994 Rev N

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to
1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT
connection to 4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to
phase-neutral

Block Impedance
Elements

Disabled
(unchecked)

Alarm Configuration, Fuse Loss
(60FL)

Disables fuse loss
protection

Element Mode

Both

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Enables both the non
voltage control and
voltage control
elements

Directional
Supervision Angle

–45.0

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the supervisory
angle to

–45°

mho Characteristic 1
Diameter
(secondary ohm)

10.0

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the first mho
characteristic diameter
to 10.0

mho Characteristic 1
Offset
(secondary ohm)

5.0

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the first mho
characteristic offset to
5.0

mho Characteristic 1
Time Delay (ms)

2,000

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the non voltage
control 40Z time delay
to 1,000 ms

mho Characteristic 1
Voltage Pickup
(secondary V)

8

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the supervisory
voltage inhibit to 10V

mho Characteristic 1
Voltage Time Delay
(ms)

1,000

Protection, Impedance, Loss of
Excitation – Impedance Based (40Z)

Sets the voltage
controlled 40Z time
delay to 2,000 ms

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 313.

Blocking is disabled.

OUT1 closes for non-voltage control trip.

OUT2 closes for non-voltage control pickup

OUT3 closes for voltage control trip.

OUT4 closes for voltage control pickup.

Fault recording is enabled.

Step 3: Prepare to monitor the 40Z function operation. Operation can be verified by monitoring OUT2

(40Z pickup) and OUT4 (40Z VC pickup, see Figure 313).

Step 4: Connect and apply balanced three-phase 2.0

∠90° A, 2.0∠330° A, 2.0∠210° A to terminals D1

through D6 and a balanced three-phase 11.0

∠0° V, 11.0∠240° V, 11.0∠120° V phase-neutral

voltage source to terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (Neutral).
All outputs should remain open.

Step 5: Slowly decrease the voltage level until OUT2 closes. Record the pickup. This should occur at

10V

±0.3 V. Verify that there is a 40Z-Z1 target on the front-panel display.

Step 6:

Continue decreasing the voltage until OUT4 closes (VC pickup). Record the pickup. This should
occur at 8V

±0.08V. Slowly increase voltage until OUT4 opens. Continue increasing until OUT2

Loss of Excitation – Impedance Based (40Z) Test

BE1-11g