Basler Electric BE1-11g User Manual

Page 597

Advertising
background image

9424200994 Rev N

585

The K factor gives the time that a generator can withstand 1 per unit negative sequence current. For
example, with a K factor of 20, since (I

2

)

2

becomes 1 at 1 per unit of current, the generator can withstand

the condition for 20 seconds. Typical values for generator K factors are in the 2 to 40 range. The BE1-11g
uses the “nominal current” setting of the BE1-11g to determine what corresponds to 1 per unit current in
the generator.

When curve 46 is selected, the BE1-11g changes the range of the allowed time dial to 1 to 99 (instead of
the time dial range of 0.1 to 9.9 for all the other curves). The user should enter the “K” factor of the
generator into the time dial field.

BE1-11g Equation

When the 46 function is used, the BE1-11g uses the K factor (i.e., 46 time dial setting), 46 minimum
pickup setting and generator full-load current to create a constant Z (see Equation 30).

𝑍 = 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �

𝐼

𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔�

2

Equation 30

The time to trip equation used in the BE1-11g is:

𝑇

𝑇

=

𝑍

𝑀

2

+ 0.028 𝑠𝑒𝑐𝑜𝑛𝑑𝑠

Equation 31

where:

𝑀 =

𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑 𝐼

2

46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

Equation 32

which, when M > 1, reduces to:

𝑇

𝑇

= 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �

𝐼

𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔

𝐼

2

𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑�

2

Equation 33

BE1-11g

Time Curve Characteristics

Advertising