Basler Electric BE1-11g User Manual
Page 597

9424200994 Rev N
585
The K factor gives the time that a generator can withstand 1 per unit negative sequence current. For
example, with a K factor of 20, since (I
2
)
2
becomes 1 at 1 per unit of current, the generator can withstand
the condition for 20 seconds. Typical values for generator K factors are in the 2 to 40 range. The BE1-11g
uses the “nominal current” setting of the BE1-11g to determine what corresponds to 1 per unit current in
the generator.
When curve 46 is selected, the BE1-11g changes the range of the allowed time dial to 1 to 99 (instead of
the time dial range of 0.1 to 9.9 for all the other curves). The user should enter the “K” factor of the
generator into the time dial field.
BE1-11g Equation
When the 46 function is used, the BE1-11g uses the K factor (i.e., 46 time dial setting), 46 minimum
pickup setting and generator full-load current to create a constant Z (see Equation 30).
𝑍 = 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �
𝐼
𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔�
2
Equation 30
The time to trip equation used in the BE1-11g is:
𝑇
𝑇
=
𝑍
𝑀
2
+ 0.028 𝑠𝑒𝑐𝑜𝑛𝑑𝑠
Equation 31
where:
𝑀 =
𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑 𝐼
2
46 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
Equation 32
which, when M > 1, reduces to:
𝑇
𝑇
= 46 𝑇𝑖𝑚𝑒 𝐷𝑖𝑎𝑙 �
𝐼
𝑁𝑜𝑚 𝑆𝑒𝑡𝑡𝑖𝑛𝑔
𝐼
2
𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑�
2
Equation 33
BE1-11g
Time Curve Characteristics