424

9424200994 Rev N

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 291.

•

Blocking is disabled.

•

OUT1 closes for 78V Trip.

•

OUT2 closes for 78V Pickup.

•

Fault recording is enabled.

Figure 291. BESTlogicPlus Settings

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Vector Jump (78V) screen and send the

first row of test settings in Table 173 to the BE1-11g.

Table 173. Pickup Test Settings

Pickup Setting

20

°

90

°

Step 4: Prepare to monitor the 78V function operation. Operation can be verified by monitoring OUT1

(see Figure 291).

Step 5: Connect and apply a three-phase 120 V phase-phase voltage source to terminals C13 (A-

phase) and C16 (Neutral).

Step 6: Apply a ±20 degree step change to the A-phase voltage angle. Verify OUT1 closes and record

the pickup. Verify that there is a 78V target on the front-panel display. Total time to trip should
be 150 ms or less. Remove the A-phase voltage angle. Verify that OUT1 opens and record the
reset. Reset the target.

Step 7: Verify the pickup accuracy and reset for a pickup setting of 90

° as listed in Table 173. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Functional Test Report

Pickup Verification

Pickup Setting Range = 2 to 90

°

Pickup Accuracy =

±1°

Step

Pickup Setting

Low

Actual Pickup

High

Pass/Fail

6

20

°

19

°

21

°

P / F

7

90

°

89

°

91

°

P / F

Vector Jump (78V) Test

BE1-11g