Functional test report, Pickup verification – Basler Electric BE1-11g User Manual
Page 436

424
9424200994 Rev N
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 291.
•
Blocking is disabled.
•
OUT1 closes for 78V Trip.
•
OUT2 closes for 78V Pickup.
•
Fault recording is enabled.
Figure 291. BESTlogicPlus Settings
Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Vector Jump (78V) screen and send the
first row of test settings in Table 173 to the BE1-11g.
Table 173. Pickup Test Settings
Pickup Setting
20
°
90
°
Step 4: Prepare to monitor the 78V function operation. Operation can be verified by monitoring OUT1
Step 5: Connect and apply a three-phase 120 V phase-phase voltage source to terminals C13 (A-
phase) and C16 (Neutral).
Step 6: Apply a ±20 degree step change to the A-phase voltage angle. Verify OUT1 closes and record
the pickup. Verify that there is a 78V target on the front-panel display. Total time to trip should
be 150 ms or less. Remove the A-phase voltage angle. Verify that OUT1 opens and record the
reset. Reset the target.
Step 7: Verify the pickup accuracy and reset for a pickup setting of 90
° as listed in Table 173. Record
the results.
Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.
Functional Test Report
Pickup Verification
Pickup Setting Range = 2 to 90
°
Pickup Accuracy =
±1°
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
6
20
°
19
°
21
°
P / F
7
90
°
89
°
91
°
P / F
Vector Jump (78V) Test
BE1-11g