Figure 71. Phase Current Differential Settings Screen
Figure 72. Phase Current Differential Operation Chart
Table 41. Operational Settings
Setting
Range
Increment
Unit of
Measure
Default
87 Mode
Disabled, Percent Differential, or
Flux Balance
n/a
n/a
Disabled
Slope Mode
Maximum or Average
n/a
n/a
Maximum
Minimum Restrained
Pickup
0 or 0.1 to 1
0.01
n/a
0
Restraint Slope 1
5 to 100
1
percent
45
BE1-11g
0BPhase Current Differential (87) Protection