Een (figure 71), Figure 72), N table 41 – Basler Electric BE1-11g User Manual

Page 127

Advertising
background image

9424200994 Rev N

115

Figure 71. Phase Current Differential Settings Screen

Figure 72. Phase Current Differential Operation Chart

Table 41. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

87 Mode

Disabled, Percent Differential, or

Flux Balance

n/a

n/a

Disabled

Slope Mode

Maximum or Average

n/a

n/a

Maximum

Minimum Restrained

Pickup

0 or 0.1 to 1

0.01

n/a

0

Restraint Slope 1

5 to 100

1

percent

45

BE1-11g

0BPhase Current Differential (87) Protection