Typical application – Basler Electric BE1-11g User Manual

Page 150

Advertising
background image

138

9424200994 Rev N

Table 51. Operational Settings

Setting

Range

Increment

Unit of

Measure

Default

Mode

Disabled, Non-Voltage Control,

Voltage Control, or Both

n/a

n/a

Disabled

Directional Supervision

Angle

–90 to 0

0.1

degrees

–15

Diameter 1

0.1 to 100 (5A CTs)
0.5 to 500 (1A CTs)

0.1

ohms

1

Diameter 2

0.1 to 100 (5A CTs)
0.5 to 500 (1A CTs)

0.1

ohms

1.4

Offset 1 & 2

0 to 110 (5A CTs)
0 to 550 (1A CTs)

0.1

ohms

1.1

Time Delay 1 & 2

0 to 300,000

varies

milliseconds

0

Voltage Pickup 1 & 2

0 or 5 to 180

1

volts

0

Voltage Time Delay 1 & 2

0 to 300,000

varies

milliseconds

0

Typical Application

Settings and measurements are used to determine if the measured system impedance is within the
tripping criteria to indicate loss of excitation.

This consists of two mho circles with the lower edge offset from the R axis by an equal distance typically
set to 1.1

*Xd. The diameter of the smaller circle (Z1) is typically set so that the upper edge is located at

X’d/2 below the R axis. The larger circle (Z2) and the directional blocking are both set to coordinate with
the steady-state stability limit of the generator. The larger circle has a time delay to prevent nuisance
tripping. Refer to Figure 87.

Figure 87. Typical Application

X

Offset

Z1 Diameter

Z2 Diameter

R

Blinder Angle

P0037-02

01-16-06

Loss of Excitation - Impedance Based (40Z) Protection

BE1-11g

Advertising