Bestnet™plus, Real time data, Bestnet – Basler Electric BE1-11g User Manual

Page 253: Plus, Bestnetplus, Bestnet ™ plus, Status page

Advertising
background image

9424200994 Rev N

241

BESTnet

Plus

BE1-11g Generator Protection Systems with an Ethernet port have a web page interface that can be used
to view BE1-11g status, real-time data, demand data, faults, sequence of events, and power quality. Refer
to the

Communication

chapter for information about configuring the BE1-11g to communicate through the

Ethernet port. Verify that Enable Web Pages is selected on the Settings, Communications, Ethernet
screen in the Settings Explorer of BESTCOMSPlus

® or on the Settings > Communication > Ethernet

screen of the front-panel display. Using a web browser, enter the IP Address of your BE1-11g in the
address bar. The protection system’s IP address is found on the front-panel display under Settings >
Communication > Ethernet. Figure 173 shows an example for a BE1-11g with an IP address of
10.0.129.101.

Figure 173. Address Bar of Web Browser

Status Page

Figure 174 illustrates the Status (home) page. Device information, firmware version, breaker status,
lockout status, recloser status, alarm status, targets, local inputs status, and local outputs status are
shown on this page. A green indicator lights to indicate an energized state for inputs and outputs.

Figure 174. Status Page (Home Page)

Real Time Data

Figure 175 illustrates the Real Time Data page. Values for currents, frequency, voltages, and power are
shown on this page.

BE1-11g

BESTnet

Plus