Setting

Value

BESTCOMSPlus Screen

Description

Element Mode

IG

Protection, Current, Instantaneous
Overcurrent (50-1)

Enables 50-1 function for IG
mode

Source

CT Circuit 1

Protection, Current, Instantaneous
Overcurrent (50-1)

Selects CT circuit 1 as the
source

50-1 IND GND

Enabled

Target Configuration, Targets

Enables IND GND target for
50-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 299.

Blocking is disabled.

OUT1 closes for 50-1 Trip.

OUT2 closes for 50-1 Pickup.

Fault recording is enabled.

Figure 299. BESTlogicPlus Settings (IG Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the low range test settings (minimum pickup setting) to the BE1-11g for your sensing
input type in Table 191.

Table 191. Pickup Test Settings (IG Mode)

Sensing Input Type

Range

Pickup Setting

Time Delay

5 A

Low

0.5 A

0 ms

Middle

5.0 A

0 ms

High

10.0 A

0 ms

1 A or SEF

Low

0.1 A

0 ms

Middle

1.0 A

0 ms

High

2.0 A

0 ms

Step 4: Prepare to monitor the 50-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 299).

Step 5: Connect a current source to terminals D7 and D8 (IG).

Step 6: Slowly increase the ground current until OUT2 closes and record the pickup. Verify that there is

a 50-1-IND GND target on the front-panel display. Slowly decrease the applied current until
OUT2 opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 50-2, 50-3, 50-4, 50-5, and 50-6.

BE1-11g

Instantaneous Overcurrent (50) Test