Operational settings – Basler Electric BE1-11g User Manual

Page 141

Advertising
background image

9424200994 Rev N

129

Operational Settings

Loss of excitation - reverse var based element operational settings are configured on the Loss of
Excitation - Reverse var Based (40Q) settings screen (Figure 82) in BESTCOMSPlus. Setting ranges and
defaults are summarized in Table 47.

Figure 82. Loss of Excitation - Reverse var Based Settings Screen

Table 47. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Pickup

0 or 1 to 6,000 (5A CTs)
0 or 1 to 1,200 (1A CTs)

varies

vars

0

Time Delay

0 or 1 to 600,000

varies

milliseconds

0

BE1-11g

Loss of Excitation - Reverse Var Based (40Q) Protection