Operational settings – Basler Electric BE1-11g User Manual
Page 141
Advertising

9424200994 Rev N
129
Operational Settings
Loss of excitation - reverse var based element operational settings are configured on the Loss of
Excitation - Reverse var Based (40Q) settings screen (Figure 82) in BESTCOMSPlus. Setting ranges and
defaults are summarized in Table 47.
Figure 82. Loss of Excitation - Reverse var Based Settings Screen
Table 47. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Pickup
0 or 1 to 6,000 (5A CTs)
0 or 1 to 1,200 (1A CTs)
varies
vars
0
Time Delay
0 or 1 to 600,000
varies
milliseconds
0
BE1-11g
Loss of Excitation - Reverse Var Based (40Q) Protection