Functional test report, Figure – Basler Electric BE1-11g User Manual

Page 556

Advertising
background image

544

9424200994 Rev N

Figure 330. BESTlogicPlus Settings

Step 5: Place the 101 in the CLOSE position by using the Metering Explorer in BESTCOMSPlus to

open the Control, Breaker Control Switch tree branch. Click on the CLOSE button to select it.
Login may be required. The green selection LED will begin to flash. Within 25 seconds, click on
the CLOSE button a second time to operate it. The green selection LED will stop flashing and
the close status LED will light.

Result: OUT3 closes for 200 ms and returns to the open state. OUT4 closes (CLOSE state) and remains
closed.

Figure 331 illustrates the breaker control switch state diagram.

Figure 331. Breaker Control Switch State Diagram

Functional Test Report

Pass/Fail

P / F

Trip

TSC

Close

CSC

P

0

0

3

5

-3

9

0

2

-2

4

-0

6

Breaker Control Switch (101) Test

BE1-11g