Step 4: Gradually decrease the magnitude all three phase voltages until OUT2 closes. Record the time

to trip (OUT1 closes). Verify that the 21-1-AB, 21-1-BC, and 21-1-CA targets are displayed on
the front-panel display. Increase the voltage until OUT2 opens. Reset the target.

Step 5:

Repeat step 4 for the time delays in the second and third rows of Table 231. Record the results.
Timing accuracy is 0.5% or 2 cycles, whichever is greater.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 21-2.

Functional Test Report

Pickup Verification Table 2 Row 1

Diameter Setting Range = 0 – 500 secondary

Pickup Accuracy =

±2% or ±0.1 Ω, whichever is greater

Reset Hysteresis = 105% of the diameter setting

Reset Accuracy =

±2% or ±0.1 Ω, whichever is greater

Step

Pickup Setting

Low

Actual Pickup

High

Low

Actual Reset

High

Pass/Fail

6

45.28 Vpn

43.71 V

46.85 V

46.26 V

48.15 V

P / F

Pickup Verification Table 2 Row 2

Step

Pickup Setting

Low

Actual Pickup

High

Low

Actual Reset

High

Pass/Fail

6

42.71 Vpn

41.23 V

44.19 V

48.72 V

50.44 V

P / F

Pickup Verification Table 2 Row 3

Step

Pickup Setting

Low

Actual Pickup

High

Low

Actual Reset

High

Pass/Fail

6

4.34 Vpn

3.84 V

4.84 V

5.86 V

7.59 V

P / F

Timing Verification

Time Delay Range = 0 to 300,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

100 ms

83.3 ms

117 ms

P / F

5

60,000 ms

57,000 ms

63,000 ms

P / F

5

0 ms

>0 ms

33.3 ms

P / F


BE1-11g