27p - phase undervoltage protection – Basler Electric BE1-11g User Manual
Page 566

554
9424200994 Rev N
Voltage Controller
Volt Pulse Width
Setting Range ........................................................... 0.1 to 5 seconds
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
Volt Pulse Interval
Setting Range ........................................................... 0.2 to 10 seconds
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
Frequency Controller
Frequency Pulse Width
Setting Range ........................................................... 0 to 99.9 seconds
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
Frequency Pulse Interval
Setting Range ........................................................... 0 to 99.9 seconds
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
Sensing Setup
Angle Compensation Setting Range ......................... 0 to 359.9
°
Voltage Monitoring
Live/Dead Voltage
Setting Range ........................................................... 0 to 90%
Accuracy....................................................................
±2%
Drop Out Delay
Setting Range ........................................................... 50 to 60,000 ms
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
27P - Phase Undervoltage Protection
Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Reset/Pickup Ratio .................................................... 102%
±1%
Inhibit Level
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Reset/Inhibit Ratio ..................................................... 102%
±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±0.5% or ±2 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................
±5% or ±2 cycles, whichever is greater
Refer to the
chapter for
information on available timing curves.
Specifications