12 warning, Warning – Westermo PMI-110-F2G User Manual

Page 125

Advertising
background image

4.12 Warning 

PMI Switch provides several types of Warning features for you to remote monitor 
the status of end devices or the change of your network. The features include 
Fault Relay, System Log and SMTP E‐mail Alert. 

Following commands are included in this group: 

4.12.1 Fault Relay 

4.12.2 Event & E‐mail warning   

4.12.2.1 Event Selection 

4.12.2.2 Syslog configuration 

4.12.2.2 SMTP Configuration 

4.12.3 CLI Commands 

 

4.12.1 Fault Relay 
 
The PMI Switch provides 1 alarm relay output, also known as Digital Output. The relay 
(DO) contact is energized from normal and will form a close circuit under system fault 
conditions.The fault conditions include power failure, Ethernet port link fault, Ring 
topology change, Ping Failure, DI state change or ping remote IP address failure. 

From the firmware version 1.1a, the fault relay supports multiple event relay binding 
function. That means fault realy not only support one event only, it can be assigned 
multiple event. The condition or term described as following table. 

Term 

conditction

description

Power 

Power DC1 

Power DC2 

Any 

Detect power input status. If one of condiction 
occurred, relay triggered. 

Port Link 

Port number

Monitoring port link down event

Ring 

Ring failure 

If ring topology changed 

Ping 

IP Address: remote device’s IP address. 

If  target  IP  does  not  reply  ping  request,  then 
relay active. 

Ping Reset 

IP address: remote device’s address 

Reset Time: duration of output open. 

Hodl Time: duration of Ping hold time. 

Ping target device and trigger relay to emulate 
power  reset  for  remote  device,  if  remote 
system crash. 

Note:  once  perform  Ping  reset,  the  relay 
output will form a short circuit. 

Dry Output 

On  period:  duration  of  relay  output  short 
(close). 

Off period: duration of relay output open. 

Relay  continuous  perform  On/Off  behavior 
with different duration. 

DI 

DI number 

Relay  trigger  when  DI  states  change  to  Hi  or 

121