Connecting the power cables for psr650-d dc psus – H3C Technologies H3C WX6000 Series Access Controllers User Manual

Page 31

Advertising
background image

23

Figure 16 Appearance of the PSR650-A

1: Power receptacle

2: Power LED

3: Power switch

4: PSU handle

Follow these steps to connect the power cord for an AC PSU:

Step1

Make sure that the PGND of the access controller is correctly connected.

Step2

Set the power switch on all the PSUs to the OFF position.

Step3

Plug one end of the supplied AC power cord into the power receptacle on the PSU and secure the power

cord by placing the bail latch over it.

Step4

Plug the other end of the power cord into the prepared AC outlet socket.

Step5

Set the power switch on the PSU to the ON position.

Step6

Check the power LED on the front panel of the access controller. LED green indicates that the PSU is

operational; LED red indicates that the PSU is faulty.

Connecting the power cables for PSR650-D DC PSUs

CAUTION:

Power off all power sources related to the access controller before connecting the DC power cables.

To avoid wrong connections, carefully check the labels on the DC power cables before making a
connection.

DC input voltage range: –48 VDC to –60 VDC, 25 A.

Figure 17 Appearance of the PSR650-D

1

2

3

4

5

6

1: RTN (+) terminal of DC input

2: Power LED

3: PSU handle

4: Power switch (ON/OFF)

5: NEG (–) terminal of DC input (–48 to –60 V)

6: PGND terminal