Codes, Troubleshooting by alarm, Cent’d) – Yaskawa i80M Maintenance Manual User Manual

Page 96: Alarm 1099 (temperature alarm inside the panel)

Advertising
background image

4.2

TROUBLESHOOTING BY ALARM

CODES

(Cent’d)

4.2.4

ALARM 1099 (TEMPERATURE ALARM INSIDE THE PANEL)

Table 4.6

Cause of Trouble

Ambient temperature of
NC rack exceeded the
specified value (70 “C 3 “C)
by measuring at top of

or

as a

result of fan failure.

Failure of power supply
unit

or CPS-16F)

(

Temperature detector is
built inside the power
supply unit.

)

Ambient temperature of
NC panel is too high.

(Applicable temperature

range is O

+40 ‘C. )

Check Method

Open NC panel door and ensure that
the fan runs normally.
Ensure that air comes out of exhaust
port at the cooling duct.
Ensure that air intake port of cooling
duct is not blocked.

Turn OFF power supply, open the

door of NC panel and cool it for
about 30 min.
If the alarm still lights.

Measure the ambient temperature.

The temperature may rise if NC

panel is exposed to direct rays of the

sun.

Solution

Replace the fan if faulty.

Call our service person-
nel Yaskawa representa-
tive
If cooling duct is
clogged, remove the
cause of clogging and
restart the operation.

l’he power supply unit

be NC placed.

Yaskawa

(Y ASREP).

Reduce the effects of

temperature rise by
shielding the NC unit,
etc.