Communications parameters, Communication parameters, Rs-232 communication – Yaskawa G7 Modbus Communication User Manual

Page 13

Advertising
background image

13

Communication Parameters

The following communications parameters affect communication over RS-232, RS-422 and RS-485 networks. The RS-232 communication

parameters are fixed. In addition, the node address is ignored when communicating via RS-232.

H5 group communication parameters can only be changed via the drive keypad.

Note: Drive power must be cycled for changes to H5 Group parameters to be recognized.



RS-232 Communication

The RS-232 communications parameters are fixed at the values shown below. Although the node address is ignored, the master when

communicating to the G7 drive in this method typically uses a node address of 1.

Table 1.1 RS-232 (RJ-45 port) Communication Parameters

Value

Description

Baud rate

9600

Parity None

Stop Bits

1

Node Address

N/A



RS-422/RS-485 Communication



Node Address – H5-01. The node address is set through G7 drive parameter H5-01. When communicating via RS-422 or RS-485, a

unique node address between 0 and 20h (32 decimal), inclusive, must be entered. The default G7 drive address is 1Fh (31 decimal).

The address is always entered as a hexadecimal number (refer to the conversion chart in Chapter 4). Address 0 is typically reserved for

global messages.



Baud Rate – H5-02. Select the baud rate that matches the controller’s communication configuration.

Table 1.2 Baud Rate – Parameter H5-02

Value

Description

0 1200bps

1 2400bps

2 4800bps

3

9600bps (Default Setting)

4 19,200bps



Parity – H5-03. Select the parity that matches the controller’s communication configuration.

Table 1.3 Parity – Parameter H5-03

Value

Description

0

None (Default Setting)

1 Even

2 Odd