Monitor Registers (Read Only)

The following table lists monitor parameters for the G7 drive. These parameters are used to monitor G7 drive information and cannot be written.



The “U-##” column contains the reference, if it exists, to the “U” monitor, parameter displayed via the operator keypad.



The “Address” column contains the register addresses for that parameter in hexadecimal format. G7 drive registers are always referred

to in hexadecimal format.



The “Function” column contains the register name.



The “Bit” column contains the list of available bits for that register. If the “Bit” column is empty, the register contains word data and

the individual bits are meaningless.



The “Description” column contains a short description of each register or register bit.



Reserved registers and data are meaningless and should be ignored.

Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

0h Run

1h Reserved

2h Reserved

3h Fault

Reset

Signal

4h Speed

Agree

5h Inverter

Ready

6h Minor

Fault

(Alarm)

7h Major

Fault

8h Reserved

9h Reserved

Ah Reserved

Bh Reserved

Ch Reserved

Dh Reserved

Eh

Frequency Reference Source (0 = b1-01 Setting, 1 = Modbus Communication)

0010h

Inverter

Status

Fh

Run Command Source (0 = b1-02 Setting, 1 = Modbus Communication)

0h

OPE - Keypad Setting Error

1h

ERR - EEPROM Write Failure

2h

PRG - Keypad Programming Mode

3h

0: Digital Operator Present, 1: PC Connected

0011h

Operator

Status

4h-Fh Reserved

0h Reserved

1h

OPE01 - drive kVA Setting Error (O2-04)

2h

OPE02 - Parameter Setting Out of Range

3h

OPE03 - Multi-Function Digital Input Setting Error

4h Reserved

5h

OPE05 - Run Command Selection Error - Option Card Missing

6h

OPE06 - Control Method Selection Error - PG Option Card Missing

7h

OPE07 - Multi-Function Analog Input Selection Error

8h

OPE08 - Function Selection Error for Current Control Mode

9h

OPE09 - PID Control Setup Error

Ah

OPE10 - V/F Parameter/Pattern Setting Error

Bh

OPE11 - Carrier Frequency Setting Error

Ch Reserved

Dh Reserved

Eh Reserved

0012h

OPE – Keypad Setting Error

Fh

Reserved