Protocol

The parameter access method supported by the G7 drive is a subset of the Modbus

communication protocol, which Yaskawa refers to as

MEMOBUS. The G7 drive supports Modbus functions 3, 6, 8 and 10h. The message format varies depending upon the function code of the

message. For each function code, there is a command message from the master and a response message from the slave. The following sections

review the format of the command and response messages for each function.



Message Functions Supported

The following table lists the Modbus function codes available and their minimum and maximum byte lengths.

Table 2.1 Supported Function Codes

Command Message

Response Message (Normal)

Function Code

Function

Minimum (bytes)

Maximum (bytes)

Minimum (bytes)

Maximum (bytes)

3h (3 dec)

Read Multiple Registers

8

8

7

21

6h (6 dec)

Write Single Register

8

8

8

8

8h (8 dec)

Loop-Back Test

8

8

8

8

10h (16 dec)

Write Multiple Registers

11

25

8

8