38

4:

Send a message from the controller to the G7 drive.

4.1:

Connect an oscilloscope between the G7 drive’s R+ and R- terminals for RS-422/RS-485 4-wire networks or between
terminals R+/S+ and R-/S- for RS-485 2-wire networks.

4.1.1:

Verify that the message pulse train exists and contains the correct number of pulses. Refer to the chapter
Message Formats for information on the message contents.

4.1.2:

Verify that the signal levels adhere to the RS-422/RS-485 standard.

4.2:

Insert a data analyzer in the RS-422/RS-485 circuit and capture the message sent by the controller in a hexadecimal
format. Record the command message below.

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

4.3:

Verify that the contents of the message adhere to the Modbus format as described previously.

4.3.1:

Verify that the node address is valid.

4.3.2:

Verify that the function code is valid.

4.3.3:

Verify that the register address is valid.

4.3.4:

Verify that the number of data bytes is valid.

4.3.5:

Verify that the CRC is correctly calculated.

4.3.6:

Verify that the message requires a response.