No response, Error codes – Yaskawa G7 Modbus Communication User Manual

Page 29

Advertising
background image

29

No Response

The slave disregards the command message and does not return a response message in the following cases:

1.

In broadcasting of data (slave address is 0), all slaves execute, but do not respond.

2.

When a communication error (overrun, framing, parity, or CRC-16) is detected in the command message.

3.

When the slave address in the command message does not coincide with the address set in the slave.

4.

When it takes longer than 2 seconds to send a message.

5.

When the time interval between characters exceeds 3.5 ms.

6.

When the command message data length is not proper.

Error Codes

Table 2.14 Fault Codes

Code

Fault

Description

1

Function Error

Invalid or unsupported function code in command message

2

Invalid Register

Invalid register address

3

Invalid Number of Registers

Invalid command message quantity

21

Data Limits Exceeded

The write command message data is out of range for the requested register

22

Write Failure

The register to be written is write protected