Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

0000: G5

1000: V7

2010: G7

2020: F7C (YEG)

2030: F7A (YEC)

2040: F7U (YEA)

2050: G7C (YEG)

2060: G7A (YEC)

2070: G7U (YEA)

0013h

Inverter

Product

Code

-

-

0h

PUF - DC Bus Fuse Failure

1h

UV1 - Main Circuit Undervoltage

2h

UV2 - Control Circuit Undervoltage

3h

UV3 - Pre-charge Contactor Answerback Failure

4h Reserved

5h

GF - Ground Fault

6h OC

-

Over

Current

7h

OV - Overvoltage

8h

OH - Inverter Overheat

9h

OH1 - Inverter Overheat Warning

Ah

OL1 - Motor Overload

Bh

OL2 - Inverter Overload

Ch

OL3 - Overtorque Detection 1

Dh

OL4 - Overtorque Detection 2

Eh

RR - Braking Resistor Failure

0014h

Fault Contents 1

Fh

RH - Braking Resistor Overheat

0h

EF3 - External Fault 3

1h

EF4 - External Fault 4

2h

EF5 - External Fault 5

3h

EF6 - External Fault 6

4h

EF7 - External Fault 7

5h

EF8 - External Fault 8

6h Reserved

7h

OS - Overspeed

8h

DEV - Speed Deviation

9h

PGO - Encoder (PG) Feedback Loss

Ah

PF - Input Phase Loss

Bh

LF- Output Phase Loss

Ch

OH3 - Overheat

Dh OPR

-

Operator

Disconnected

Eh

ERR - EEPROM Write Failure

0015h

Fault Contents 2

Fh

OH4 - Motor Overheat

0h

CE - Communication Loss

1h

BUS - Communication Option Card Fault

2h

E-15 - SI-F/G Fault

3h

E-10 - SI-F/G Fault

4h

CF - Loss of Motor Control

5h

SVE - Zero Servo Fault

6h

EF0 - Communications Option External Fault

7h

FBL - PID Feedback Loss

8h

UL3 - Undertorque Detection 1

9h

UL4 - Undertorque Detection 2

Ah

OL7 - High Slip Braking Overload

Bh

EF9 - External Fault 9

Ch

EF10 - External Fault 10

Dh

EF11 - External Fault 11

Eh

EF12 - External Fault 12

0016h

Fault Contents 3

Fh Reserved

Advertising