Table 4.13 “O” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
0 No
Change
1 Set
Defaults
o2-03 0507h
User Defaults
(A1-03 = 1110)
2 Clear
All
1 0
A A A A
A
0 Disabled
o2-05 0509h
Operator
M.O.P.
Selection
1 Enabled
1 0
A A A A A
0 Disabled
o2-06 050Ah
Operator Disconnect
Detection Selection
1 Enabled
1 0
A A A A A
o2-07 050Bh
Accumulated Time Initial
Setting
0 ~ 65535 H
1 H
0 H
A
A
A
A
A
0 Power-On
Time
o2-08 050Ch
Accumulated Time
Selection
1 Running
Time
1 0
A A A A A
o2-10 050Eh
Fan Run Time Initial
Setting
0 ~ 65535 H
1 H
0 H
A
A
A
A
A
0 No
Change
o2-12 0510h
Fault Trace/History
Initialization
(U2 and U3 Monitors)
1 Clear
All
1 0
A A A A A
0 No
Change
o2-14 0512h
Watt Hour Monitors
(U1-29 and U1-30)
Initialization
1 Clear
All
1 0
A A A A A