Yaskawa G7 Modbus Communication User Manual

Page 57

Advertising
background image

57

Table 4.7 “D” Parameters

Access Level

Name

Address

Description

Data

Range

Unit

Default

During

Run

V/f

V/f

w/PG

OLV

FV

OLV2

d1-01

0280h

Frequency Reference 1

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

Q

Q

Q

Q

Q

d1-02

0281h

Frequency Reference 2

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

Q

Q

Q

Q

Q

d1-03

0282h

Frequency Reference 3

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

Q

Q

Q

Q

Q

d1-04

0283h

Frequency Reference 4

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

Q

Q

Q

Q

Q

d1-05

0284h

Frequency Reference 5

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-06

0285h

Frequency Reference 6

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-07

0286h

Frequency Reference 7

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-08

0287h

Frequency Reference 8

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-09

0288h

Frequency Reference 9

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-10

028Bh

Frequency Reference 10

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-11

028Ch

Frequency Reference 11

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-12

028Dh

Frequency Reference 12

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-13

028Eh

Frequency Reference 13

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-14

028Fh

Frequency Reference 14

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-15

0290h

Frequency Reference 15

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-16

0291h

Frequency Reference 16

0.0 ~ 400.0 Hz

0.01 Hz

0.0 Hz

R

A

A

A

A

A

d1-17

0292h

Jog Frequency Reference

0.0 ~ 400.0 Hz

0.01 Hz

6.0 Hz

R

Q

Q

Q

Q

Q

d2-01 0289h

Frequency Reference

Upper Limit

0.0 ~ 110.0 %

0.1 %

100.0 %

A

A

A

A

A

d2-02 028Ah

Frequency Reference

Lower Limit

0.0 ~ 110.0 %

0.1 %

0.0 %

A

A

A

A

A

d2-03 0293h

Analog Input Frequency

Reference Lower Limit

0.0 ~ 110.0 %

0.1 %

0.0 %

A

A

A

A

A

d3-01

0294h

Jump Frequency 1

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

d3-02

0295h

Jump Frequency 2

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

d3-03

0296h

Jump Frequency 3

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

d3-04

0297h

Jump Bandwidth

0.0 ~ 20.0 Hz

0.1 Hz

1.0 Hz

A

A

A

A

A

0 Disabled

d4-01 0298h

MOP Reference Memory

Selection

1 Enabled

1

0

A A A A A

d4-02

0299h

Trim Control Level

0 ~ 100 %

1 %

10 %

A

A

A

A

A

0 Speed

Control

d5-01

029Ah

Torque Control Selection

1 Torque

Control

1 ms

0 ms

A

A

d5-02 029Bh

Torque Reference Filter

Time

0 ~ 1000 ms

1 ms

Cntrl Meth

A

A

1 Soft

Starter

Output

d5-03 029Ch Speed

Limit

Selection

2 d5-04

Setting

1 1

A

A

d5-04

029Dh

Speed Limit Value

-120 ~ 120 %

1 %

0 %

A

A

d5-05

029Eh

Speed Limit Bias

0 ~ 120 %

1 %

10 %

A

A

d5-06 029Fh

Speed/Torque

Changeover Hold Time

0 ~ 1000 ms

1 ms

0 ms

A

A

0 Disabled

d5-07 02A6h

Directional Speed Limit

Selection

1 Enabled

1

1 A

d6-01 02A0h Field-Weakening

Level

0 ~ 100 %

1 %

80 %

A

A

d6-02 02A1h

Field-Weakening

Frequency

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

0 Disabled

d6-03

02A2h

Field Forcing Selection

1 Enabled

1 0

A

A

A

d6-05 02A4h

AR Time Gain

0.0 ~ 10.0

0.01

1

A

d6-06

02A5h

Field Forcing Limit

100 ~ 400 %

1 %

400 %

A

A

A