Yaskawa G7 Modbus Communication User Manual

Page 46

Advertising
background image

46

Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

0h Reserved

1h Reserved

2h CPF02

3h CPF03

4h CPF04

5h CPF05

6h CPF06

7h CPF07

8h CPF08

9h CPF09

Ah CPF10

0017h

CPF Contents 1

Bh-Fh Reserved

0h CPF20

1h CPF21

2h CPF22

3h CPF23

0018h

CPF Contents 2

4h-Fh Reserved

0h

UV - Undervoltage

1h

OV - Overvoltage

2h

OH - Inverter Overheat

3h

OH2 - Inverter Overheat Warning

4h

OL3 – Overtorque Detection 1

5h

OL4 – Overtorque Detection 2

6h

EF - 2-wire Sequence Input Fault

7h BB

-

Baseblock

8h

EF3 - External Fault 3

9h

EF4 - External Fault 4

Ah

EF5 - External Fault 5

Bh

EF6 - External Fault 6

Ch

EF7 - External Fault 7

Dh Reserved

Eh Reserved

0019h

Minor

Fault

Contents

1

Fh

OS - Overspeed

0h

DEV - Speed Deviation

1h

PGO - Encoder (PG) Feedback Loss

2h OPR

-

Operator

Disconnected

3h

CE - Communication Loss

4h

BUS - Communication Option Card Fault

5h

CALL - Waiting for Communications

6h

OL1 - Motor Overload

7h

OL2 - Inverter Overload

8h

E-15 - SI-F/G Communication Fault

9h

E-10 - SI-F/G Fault

Ah

Motor Switch

(Attempting to switch Motor 1/2 during Run.

“Motor Running” is flashed on the keypad. See Motor 2 Selection, H1-XX = 16)

Bh

FBL - PID Feedback Loss

Ch

CALL - Waiting for Initial Communication after Power Up

Dh

UL3 - Undertorque Detection 1

Eh

UL4 - Undertorque Detection 2

001Ah

Minor

Fault

Contents

2

Fh



Communication Test Fault

(Attempting to perform communication self-test during run.

“SE” is flashed on the keypad. See Communication Self-test, H1-XX = 67)




Advertising