Yaskawa G7 Modbus Communication User Manual

Page 47

Advertising
background image

47

Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

0h

OH3 - Motor Overheat Alarm

1h

Drive Not Enabled

(Attempting to run when drive Enable input is not closed.

See drive Enable, H1-XX = 6A)

001Bh

Minor Fault Contents 3

2h-Fh Reserved

0h Run

1h Reverse

Direction

2h Inverter

Ready

3h Fault

4h

Data Setting Error

5h

Multi-Function Digital Output 1 (M1-M2)

6h

Multi-Function Digital Output 2 (M3-M4)

7h

Multi-Function Digital Output 3 (M5-M6)

8h

Multi-Function Digital Output 4 (P3-C3)

9h

Multi-Function Digital Output 5 (P4-C4)

0020h

Inverter Status

Ah-Fh

Reserved

0h

OC or GF - Overcurrent/Ground Fault

1h

OV - Overvoltage

2h

OL2 - Inverter Overload

3h

OH1 or OH2 - Overheat Fault

4h

RR or RH - Braking Resistor Fault

5h

PUF - DC Bus Fuse Failure

6h

FBL - PID Feedback Loss

7h

EFx or EFO - External Fault

8h

CPF - Control Board Hardware Fault

9h

OL1, or OL3, or OL4 - Motor Overload/Overtorque 1 or 2

Ah

PGO, OS, or DEV - Speed Feedback

Bh

UV - Undervoltage

Ch

UV1, UV2, or UV3 - Undervoltage

Dh

SPI or SPO - Input/Output Phase Loss

Eh

CE - Communication Loss

0021h

Fault Contents

Fh OPR

-

Operator

Disconnected

0 Writing

Data

1 Reserved

2 Reserved

3

Upper or Lower Data Limit Error

4

Data Integrity Error

0022h

Data Link Status

5h-Fh Reserved

U1-01

0023h

Frequency Reference Monitor

-

Scaling Dependent Upon o1-03 Setting

U1-02

0024h

Output Frequency Monitor

-

Scaling Dependent Upon o1-03 Setting

U1-06

0025h

Output Voltage Reference Monitor

-

Scaling Dependent Upon H5-10 Setting

U1-03

0026h

Output Current Monitor

-

Units 0.01A

U1-08

0027h

Output Power Monitor

-

Units 0.1kW

U1-09

0028h

Torque Reference Monitor

-







Units 0.1%