Yaskawa G7 Modbus Communication User Manual

Page 48

Advertising
background image

48

Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

0h

Terminal S1 Closed

1h

Terminal S2 Closed

2h

Terminal S3 Closed

3h

Terminal S4 Closed

4h

Terminal S5 Closed

5h

Terminal S6 Closed

6h

Terminal S7 Closed

7h

Terminal S8 Closed

8h

Terminal S9 Closed

9h

Terminal S10 Closed

Ah

Terminal S11 Closed

Bh

Terminal S12 Closed

002Bh

Digital Input Status

Ch-Fh

Reserved

0h

During Run 1 (H2-0X = 0)

1h

Zero Speed (H2-0X = 1)

2h

Speed Agree 1 (H2-0X = 2)

3h

Fref/Set Speed Agree 1 (H2-0X = 3)

4h

Frequency Detection 1 (H2-0X = 4)

5h

Frequency Detection 2 (H2-0X = 5)

6h

Inverter Ready (H2-0X = 6)

7h

Undervoltage (H2-0X = 7)

8h

Baseblock (H2-0X = 8)

9h

Frequency Reference from Digital Operator (H2-0X = 9)

Ah

Run Command from Digital Operator (H2-0X = A)

Bh

Overtorque Detection 1 (H2-0X = B)

Ch

Loss of Frequency Reference (H2-0X = C)

Dh

During Fault Retry

Eh Fault

002Ch

Inverter Status

Fh

Communication Timeout (CE Fault)

0h

Multi-Function Digital Output 1 (M1-M2)

1h

Multi-Function Digital Output 2 (M3-M4)

2h

Multi-Function Digital Output 3 (M5-M6)

3h

Multi-Function Digital Output 4 (P3-C3)

4h

Multi-Function Digital Output 5 (P4-C4)

002Dh

Digital Output Status

5h-Fh Reserved

U1-07

0031h

Main Circuit DC Bus Voltage

-

Units 1.0VDC

U1-18

0032h

Motor Secondary Current

-

Units 0.1%

U1-08

0033h

Output Power

-

Units 0.1kW

U1-24

0038h

PID Feedback Level

-

10 / 1% with sign, 100% = E1-04

U1-36

0039h

PID Input Level

-

10 / 1% with sign, ±100% / ±E1-04

U1-37

003Ah

PID Output Level

-

10 / 1% with sign, ±100% / ±E1-04

U1-28

003Bh

Drive CPU Number

-

Last 5 Digits CPU Software Number

U1-14

003Ch

Drive Software Number

-

Last 5 Digits of Software Number

0h CRC

Error

1h

Invalid Data Length Error

2h Reserved

3h Parity

Error

4h Overrun

Error

5h Framing

Error

6h Timeout

003Dh

Communication Error

7h-Fh Reserved

o2-04

003Eh

kVA Setting

-

Same Data as Parameter o2-04

U1-04

003Fh

Control Mode

-

Range = 0 ~ 4. See A1-02

U1-01

0040h

Frequency Reference

-

Scaling Dependent Upon o1-03 Setting

U1-02

0041h

Output Frequency

-

Scaling Dependent Upon o1-03 Setting

U1-03

0042h

Output Current

-

Units 0.1A

U1-04

0043h

Control Mode

-

Range = 0 ~ 4. See A1-02

U1-05

0044h

Motor Speed

-

Scaling Dependent Upon o1-03 Setting

Advertising