Yaskawa G7 Modbus Communication User Manual

Page 56

Advertising
background image

56

Table 4.6 “C” Parameters

Access Level

Name

Address

Description

Data

Range

Unit

Default

During

Run

V/f

V/f

w/PG

OLV

FV

OLV2

C1-01

0200h

Accel Time 1

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

R

Q

Q

Q

Q

Q

C1-02

0201h

Decel Time 1

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

R

Q

Q

Q

Q

Q

C1-03

0202h

Accel Time 2

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

R

A

A

A

A

A

C1-04

0203h

Decel Time 2

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

R

A

A

A

A

A

C1-05

0204h

Accel Time 3

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

A

A

A

A

A

C1-06

0205h

Decel Time 3

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

A

A

A

A

A

C1-07

0206h

Accel Time 4

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

A

A

A

A

A

C1-08

0207h

Decel Time 4

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

A

A

A

A

A

C1-09

0208h

Fast Stop Time

0.0 ~ 6000.0 Sec

0.1 Sec

10.0 Sec

A

A

A

A

A

0 0.01

Seconds

C1-10

0209h Accel/Decel

Units

1 0.1

Seconds

1

1

A A A A A

C1-11

020Ah

Accel/Decel Switchover

Frequency

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

C2-01

020Bh

S-Curve at Accel Start

0.0 ~ 2.5 Sec

0.01 Sec

0.20 Sec

A

A

A

A

A

C2-02

020Ch

S-Curve at Accel End

0.0 ~ 2.5 Sec

0.01 Sec

0.20 Sec

A

A

A

A

A

C2-03

020Dh

S-Curve at Decel Start

0.0 ~ 2.5 Sec

0.01 Sec

0.20 Sec

A

A

A

A

A

C2-04

020Eh

S-Curve at Decel End

0.0 ~ 2.5 Sec

0.01 Sec

0.00 Sec

A

A

A

A

A

C3-01

020Fh

Slip Compensation Gain

0.0 ~ 2.5

0.1

Cntrl Meth

R A A A A

C3-02

0210h

Slip Compensation Filter Time

0 ~ 10000 ms

1 ms

Cntrl Meth

A A

C3-03

0211h

Slip Compensation Limit

0 ~ 250 %

1 %

200 %

A

A

0 Disabled

C3-04

0212h

Slip Compensation During

Regeneration

1 Enabled

1

0

A A

0 Disabled

C3-05

0213h

Output Voltage Limit Selection

1 Enabled

1 0

A

A

A

C4-01

0215h

Torque Compensation Gain

0.0 ~ 2.5

0.01

1.00

R

A

A

A

C4-02

0216h

Torque Compensation Filter

Time

0 ~ 10000 ms

1 ms

Cntrl Meth

A A A

C4-03

0217h

Forward Direction Torque

Compensation at Start

0.0 ~ 200.0 %

0.1 %

0.0 %

A

C4-04

0218h

Reverse Direction Torque

Compensation at Start

-200.0 ~ 0.0 %

0.1 %

0.0 %

A

C4-05

0219h

Torque Compensation at Start

Filter Time

0 ~ 200 ms

1 ms

10 ms

A

C5-01

021Bh

ASR Proportional Gain 1

Cntrl Meth

0.01

Cntrl Meth

R A A A

C5-02

021Ch

ASR Integral Time 1

0.000 ~ 10.000 Sec

0.001 Sec

Cntrl Meth

R A A A

C5-03

021Dh

ASR Proportional Gain 2

Cntrl Meth

0.01

Cntrl Meth

R A A A

C5-04

021Eh

ASR Integral Time 2

0.000 ~ 10.000 Sec

0.001 Sec

Cntrl Meth

R A A A

C5-05

021Fh

ASR Limit

0.0 ~ 20.0 %

0.1 %

0.0 %

A

C5-06

0220h ASR

Filter Time

0.000 ~ 0.500 Sec

0.001 Sec

Cntrl Meth

A

A

C5-07

0221h

ASR Gain Switchover

Frequency

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

C5-08

0222h

ASR Integral Limit

0 ~ 400 %

1 %

400 %

A

A

C5-10

0231h ASR

Filter Time 2

0.000 ~ 0.500 Sec

0.001 Sec

0.010 Sec

A

1h Fc=2.0kHz

2h Fc=5.0kHz

3h Fc=8.0kHz

4h Fc=10.0kHz

5h Fc=12.5kHz

6h Fc=15.0kHz

C6-02

0224h Carrier

Frequency

Selection

Fh

C6-03 ~ C6-05

1 kVA

Dep.

Q Q Q Q Q

C6-03

0225h Carrier

Frequency

Maximum

0.4 ~ 15.0 kHz

(kVA Dependent)

0.1 kHz

kVA Dep.

A A A A

C6-04

0226h Carrier

Frequency

Minimum

0.4 ~ 15.0 kHz

(kVA Dependent)

0.1 kHz

kVA Dep.

A A

C6-05

0227h

Carrier Frequency Gain

0 ~ 99

1

0

A

A